1、发电厂接地系统设计规定一、GrO八dingSgSteMDeSig八接地系统设计ThegroundingandlightningprotectionsystemshallbedesignedperIEEE-80andlocalcodesandstatutes,andshallconsistofanintegratednetworkofgroundingconductorsandgroundrods.ThefinalnumberofgroundingrodsandtheactualquantityofgroundingconductorsshallbebasedupontheJobSitetopo
2、graphy,ananalysisofexistingsoildata,andtheContractorssoilresistivitytesting.Allgroundingconductorsutilizedinthegroundingsystemshallbebarezhard-drawncopperthroughout.Allgroundingrodsshallbethree(3)metersminimumlength,copper-weld-typethroughout.Allgroundingtestwellsshallbepre-castconcretethroughoutwit
3、hdistinctiveflushsurface-mountedremovablecovers.接地与防雷保护系统应根据电气与电子工程师协会-80及地方规范和法规行设计,并且应由接地导线和接地棒组成的综合接地网。接地棒的最终数量和接地导线的实际数量应根据工程现场地势条件,现有土壤数据分析,以及承包商土壤电阻率测试结果最终确定。接地系统中使用的所有接地导线应采用硬铜裸导线。所有接地棒的长度至少为三(3)米,并且应采用铜焊接地棒。所有接地测试并应采用预铸混凝土,并且配有找平安装可移除井盖。Thegroundingsystemshallbedesignedtoachievethefollowing:
4、接地系统的设计应能够满足以下条件:1. Establishaminimumresistancetoearthatalllocationsnottoexceedone(1)ohm.各位置最小接地电阻不得超过一(1)欧姆。2. Protectpersonnelfromdangerouspotentialssuchastransferred,stepandtouchpotentialsduringbothnormaloperatingandmaximumgroundfaults.保护人员免受危险影响,例如在正常操作或最大接地故障情况下发生传递电位、跨步电压或接触电压。3. Provideconnec
5、tiontogroundforpowerequipmentneutrals.为电力设备中性点提供接地。4. Facilitaterelayinginclearinggroundfaults.促进接地故障保护继电器清除接地故障。5. Safelyandeffectivelydissipatelightningcharges.安全有效地使雷电电荷消散。AllFacilityelectricalequipment,includingboththeabove-gradeandbelow-graderacewaysystems,allmotorframes,andallswitchyardapparat
6、usshallbetiedtothegroundingsystemandtoeachother.AllFacilitymechanicalapparatus,includingalloutdoorandbuildingsteelsupportcolumns,platforms,stairways,elevatedstructures,andmetallictanksandvessels,shallbetiedtothegroundingsystem.所有设施电气设备,包括地上与地下电缆管道系统.所有电机座和所有开关站装置,应与接地系统及彼此连接。所有设施机械设备,包括所有室外和建筑钢制支撑柱.
7、平台.楼梯、高架结构.金属罐和容器应与接地系统连接。InboththeGISbuildingandtheoutdoorFacilityswitchyardareas,thegroundingsystemshallbeasubsurfacerectangulargroundinggridcomposedofoverlapping240mm2minimumcopperconductor,arrayedona4.57meterx4.57metermaximumconductorspacing.Thisrectangulargroundinggridshallextendunderalltransfo
8、rmerbasinsfoundationszunderthefoundationsofallhighvoltagedisconnectswitches,undertheGISswitchgearbuildingfoundations,underallswitchyardequipmentsupportstructures,andjustbeyondtheperimeterfencingoftheswitchyard.Thediametrically-oppositecornersofallpowertransformerandlightningprotectionequipmentshallb