1、变压器试验报告安装位置1#站变试验性质交接型号Sl1-2000/10试验日期2016.05.29额定电压(KV)高压I(XXX)额定电流(A)高压115.5低压400低压2886.8额定容量(KVA)2000短路阻抗(%)5.81联接组别Dynll空载损耗(KW)/负载损耗(KW)/空载电流(%)/冷却方式ONAN出厂日期2014.09出厂编号02962制造厂家丹东欣泰变压比试验分接开关位置高压侧/低压侧实测变压比变压比误差()ABZabBC/bcCA/caAB/abBC/bcCA/ca127.47127.46127.471-0.11-0.14-0.10226.83626.83226.833-
2、0.15-0.16-0.16326.26226.25426.260+0.05+0.02+0.04425.62525.62325.617-0.00-0.01-0.03524.99524.98624.986-0.02-0.06-0.06624.35824.35424.350-0.07-0.09-0.10723.72323.71923.714-0.11-0.13-0.15823.14623.14023.140+0.09+0.07+0.07922.51122.50922.208+0.05+0.04+0.04高压绕组直流电阻(mA)别分接宜ABBCCA三相直流电阻不平衡率()1433.0433.9431
3、.90.462422.2423.0421.20.433412.3413.2411.30.464401.3401.2400.50.205390.4391.3389.80.386379.6380.5379.00.407368.7369.7368.20.418358.9359.9358.50.399348.2349.2347.90.37低压绕组直流电阻(mA)aoboCO三相直流电阻不平衡率()0.32180.32390.32711.63绝缘电阻试验试部位项目高压对低压及地低压对高压及地高压对低压铁心对地测试时间60S/15S60S/15S60S/15S60S绝缘电阻(GQ)250001300020