Condensation Control Experiences in a Building with Movable Sash.ppt
《Condensation Control Experiences in a Building with Movable Sash.ppt》由会员分享,可在线阅读,更多相关《Condensation Control Experiences in a Building with Movable Sash.ppt(21页珍藏版)》请在第壹文秘上搜索。
1、Condensation Control Experiences in an“historic”Building with Movable SashWhat are your first thoughts when you consider ceiling radiant cooling panels?Requirement for Ceiling Radiant Cooling Panel Application20-70%less OA,DOAS Unit W/Energy RecoveryCool/Dry SupplyParallel Sensible Cooling SystemHig
2、h Induction DiffuserBuilding With Sensible and Latent cooling decoupledSite for the condensation control experiences:1900s Engineering Units3 of 12 36”X 96”single glazed movable sash serving the 40 x 80 labThe Space as seen from insideSystem SchematicSize and extent of the major components in the sy
3、stemRadiant panels8 2 x 40640 ft2:4 tonChiller2 5 ton eachHigh Induction diffusers8 2 x2150 scfm eachAir handling unit with EW,MSOperated at 1200 scfmExtensive instrumentationT,flowair&water,RH,CO2DDC ControlsBACnet,web accessiblePumpsTwo circuits at 22 gpm.Condensate control method1.Maintain the pa
4、nel inlet water temperature above the space DPT 2.Condensate sensor is hard wired into the power supply of the panel spring return control valve.Field experience,student co-op?nThe lab is used by a new(but just one)group of students per yearnNear the beginning of the semester,I will address them on
5、the systemand make just a few points.Leave the doors or windows open and radiant cooling will be lostnot recommended Piling things on top of the panels will cause the cooling to be reducednot recommended Slicing the exterior duct insulation not a good idea,condensate may drip on you and your work.St
6、udents response?nThey never opened the windows or propped the doors open.The condensation control was unchallengednAn instantaneous open door and window tests on a hot humid summer day thus ensued.The data:Windows openedOA DPTRoom DPTCHWT to panelsCHWT exceeds room DPT after 22 min2.5FExtreme Conden